The Specification of Field Test Requirements
for a Balanced Twisted-Pair Cabling System
Cat 5E Installation: field test
requirements upon completion of the installation
A. General Requirements
1. Every cabling link in the installation shall
be tested in accordance with the Telecommunications Industry
Association (TIA) standard ANSI/TIA/EIA-568-B.1 (March 2001)
Section 11.2: 100-Ohm twisted-pair transmission performance
and field test requirements.
2. The installed twisted-pair horizontal links shall
be tested from the IDF in the telecommunications room to
the telecommunication wall outlet in the work area against
the "Permanent Link" performance limits specification
as defined in ANSI/TIA/EIA-568-B.1 (March 2001).
3. 100% of the installed cabling links must be tested
and must pass the requirements of the standards mentioned
in I.A.2 above and as further detailed in Section I.B. Any
failing link must be diagnosed and corrected. The corrective
action shall be followed with a new test to prove that the
corrected link meets the performance requirements. The final
and passing result of the tests for all links shall be provided
in the test results documentation in accordance with Section
I.C below.
4. Trained technicians who have successfully attended
an appropriate training program and have obtained a certificate
as proof thereof shall execute the tests. Appropriate training
programs include but are not limited to installation certification
programs provided by BICSI or the ACP (Association of Cabling
Professionals).
5. The test equipment (tester) shall comply with
or exceed the accuracy requirements for enhanced level II
(Level II-E) field testers as defined in TIA-568-B; Annex
I: Section I.4. The tester including the appropriate interface
adapter must meet the specified accuracy requirements. The
accuracy requirements for the permanent link test configuration
(baseline accuracy plus adapter contribution) are specified
in Table I.4 of Annex I of TIA/EIA-568-B.2. (Table I.5 in
this TIA document specifies the accuracy requirements for
the Channel configuration.)
6. The tester shall be within the calibration period
recommended by the vendor in order to achieve the vendor-specified
measurement accuracy.
7. The tester interface adapters must be of high
quality and the cable shall not show any twisting or kinking
resulting from coiling and storing of the tester interface
adapters. In order to deliver optimum accuracy preference
is given to a permanent link interface adapter for the tester
that can be calibrated to extend the reference plane of
the Return Loss measurement to the permanent link interface.
The contractor shall provide proof that the interface has
been calibrated within the period recommended by the vendor.
To ensure that normal handling on the job does not cause
measurable Return Loss change, the adapter cord cable shall
not be of twisted-pair construction.
8. The Pass or Fail condition for the link-under-test
is determined by the results of the required individual
tests (detailed in Section I.B). Any Fail or Fail* result
yields a Fail for the link-under-test. In order to achieve
an overall Pass condition, the results for each individual
test parameter must Pass or P ass*.
9. A Pass or Fail result for each parameter is determined
by comparing the measured values with the specified test
limits for that parameter. The test result of a parameter
shall be marked with an asterisk (*) when the result is
closer to the test limit than the accuracy of the field
tester. The field tester manufacturer must provide documentation
as an aid to interpret results marked with asterisks. (Reference
TIA-568-B; Annex I: Section I.2.2)
10. A representative of the end-user shall be invited
to witness field testing. The representative shall be notified
of the start date of the testing phase 5 business days before
testing commences.
11. A representative of the end-user will select
a random sample of 5% of the installed links. The representative
(or his authorized delegate) shall test these randomly selected
links and the results are to be stored in accordance with
the prescriptions in Section I.C. The results obtained shall
be compared to the data provided by the installation contractor.
If more than 2% of the sample results differ in terms of
the pass/fail determination, the installation contractor
under supervision of the enduser representative shall repeat
100% testing and the cost shall be borne by the installationcontractor.
B. Performance Test Parameters
The test parameters for Cat 5e are defined in ANSI/TIA/EIA
standard 568-B.1; Section 11.2.4 as well as in Annex I;
Section I.2.1 "Parameters to be reported." The
test of each Cat 5e link shall contain all of the following
parameters as detailed below. In order to pass the link
test all measurements (at each frequency in the range from
1 MHz through 100 MHz) must meet or exceed the limit value
determined in the above -mentioned Cat 5e standard.
[Optional Requirement - can only be combined with option
I.C.6.a] in Section I.C.6.] Each parameter shall be
measured from 1 through 350 MHz and all of these measurement
points are to be recorded in the test results information
as detailed in Section I.C.6.
1. Wire Map [as defined in TIA/EIA-568-B.1; Section
11.2.4.2]
Wire Map shall report Pass if the wiring of each wire-pair
from end to end is determined to be correct. The Wire Map
results shall include the continuity of the shield connection
if present.
2. Length [as defined in TIA/EIA-568-B.1; Section
11.2.4.3]]
The field tester shall be capable of measuring length of
all pairs of a permanent link or channel based on the propagation
delay measurement and the average value for NVP (1). The
physical length of the link shall be calculated using the
pair with the shortest electrical delay. This length figure
shall be reported and shall be used for making the Pass/Fail
decision. The Pass/Fail criteria are based on the maximum
length allowed for the permanent link configuration (90
meters - 295 ft) or the channel (100 meters - 328 ft) plus
10% to allow for the variation and uncertainty of NVP.
3. Insertion Loss (Attenuation) [as defined in TIA/EIA-568-B.1;
Section 11.2.4.4]
Insertion Loss is a measure of signal loss in the permanent
link or channel. The term 'Attenuation' has been used to
designate 'insertion loss'. Insertion Loss shall be tested
from 1 MHz through 100 MHz in maximum step size of 1 MHz.
It is preferred to measure attenuation at the same frequency
intervals as NEXT Loss in order to provide a more accurate
calculation of the Attenuation-to-Crosstalk Ratio (ACR)
parameter.
Minimum test results documentation (summary results): Identify
the worst wire pair (1 of 4 possible). The test results
for the worst wire pair must show the highest attenuation
value measured (worst case), the frequency at which this
worst case value o ccurs, and the test limit value at this
frequency.
4. NEXT Loss, pair-to-pair [as defined in TIA/EIA-568-B.1;
Section 11.2.4.5]
Pair-to-pair near-end crosstalk loss (abbreviated as NEXT
Loss) shall be tested for each wire pair combination from
each end of the link (a total of 12 pair combinations).
This parameter is to be measured from 1 through100 MHz.
NEXT Loss measures the crosstalk disturbance on a wire pair
at the end from which the disturbance signal is transmitted
(near-end) on the disturbing pair. The maximum step size
for NEXT Loss measurements shall not exceed the maximum
step size defined in the standards as shown in Table 1,
column 2. A smaller step size more accurately identifies
worst case margin conditions (see summary results, below).
TABLE 1
Frequency Range(MHz) |
Maximum Stepsize (MHz) |
1 - 31.25 |
0.15 |
31.26 - 100 |
0.25 |
1 Nominal Velocity of Propagation (NVP) expresses the speed
of the electrical signals along the cabling link in relation
to the speed of light in vacuum (3x108 m/second). Insulation
characteristics and twist rate of the wire pair influence
NVP in minor ways. Typically, an 'average' value for NVP
is published for all four wire-pairs in a data cable.
Minimum test results documentation (summary results): Identify
the wire pair combination that exhibits the worst case NEXT
margin (2) and the wire pair combination that exhibits the
worst value of NEXT (worst case). NEXT is to be measured
from each end of the link-under-test. These wire pair combinations
must be identified for the tests performed from each end.
Each reported case shall include the frequency at which
it occurs as well as the test limit value at this frequency.
5. PSNEXT Loss [as defined in TIA/EIA-568-B.1; Section
11.2.4.6]
Power Sum NEXT Loss shall be evaluated and reported for
each wire pair from both ends of the link-under-test (a
total of 8 results). PSNEXT Loss captures the combined near-end
crosstalk effect (statistical) on a wire pair when all other
pairs actively transmit signals. Like NEXT this test parameter
must be evaluated from 1 through 100 MHz and the step size
may not exceed the maximum step size defined in the standards
as shown in Table 1, column 2.
Minimum test results documentation (summary results): Identify
the wire pair that exhibits the worst case margin and the
wire pair that exhibits the worst value for PSNEXT. These
wire pairs must be identified for the tests performed from
each end. Each reported case shall include the frequency
at which it occurs as well as the test limit value at this
frequency.
6. ELFEXT Loss, pair-to-pair [as defined in TIA/EIA-568-B.1;
Section 11.2.4.7]
Pair-to-pair FEXT Loss shall be measured for each wire-pair
combination from both ends of the link-under-test. FEXT
Loss measures the unwanted signal coupling (crosstalk disturbance)
on a wire pair at the opposite end (far-end) from which
the transmitter emits the disturbing signal on the disturbing
pair. FEXT is measured to compute ELFEXT Loss that must
be evaluated and reported in the test results. ELFEXT measures
the relative strength of the far-end crosstalk disturbance
relative to the attenuated signal that arrives at the end
of the link. This test yields 24 wire-pair combinations.
ELFEXT is to be measured from 1 through 100 MHz and the
maximum step size for FEXT Loss measurements shall not exceed
the maximum step size defined in the standards as shown
in Table 1, column 2.
Minimum test results documentation (summary results): Identify
the wire pair combination that exhibits the worst case margin
and the wire pair combination that exhibits the worst value
for ELFEXT. These wire pairs must be identified for the
tests performed from each end. Each reported case shall
include the frequency at which it occurs as well as the
test limit value at this frequency.
7. PSELFEXT Loss [as defined in TIA/EIA-568-B.1;
Section 11.2.4.8]
Power Sum ELFEXT is a calculated parameter that combines
the effect of the FEXT disturbance from three wire pairs
on the fourth one. This test yields 8 wire-pair combinations.
Each wire-pair is evaluated from 1 through 100 MHz in frequency
increments that do not exceed the maximum step size defined
in the standards as shown in Table 1, column 2.
Minimum test results documentation (summary results): Identify
the wire pair that exhibits the worst case margin and the
wire pair that exhibits the worst value for PSELFEXT. These
wire pairs must be identified for the tests performed from
each end. Each reported case shall include the frequency
at which it occurs as well as the test limit value at this
frequency.
8. Return Loss [as defined in TIA/EIA-568-B.1; Section
11.2.4.9]
Return Loss (RL) measures the total energy reflected on
each wire pair. Return Loss is to be measured from both
ends of the link-under-test for each wire pair. This parameter
is also to be measured form 1 through 100 MHz in frequency
increments that do not exceed the maximum step size defined
in the standards as shown in Table 1, column 2.
Minimum test results documentation (summary results): Identify
the wire pair that exhibits the worst case margin and the
wire pair that exhibits the worst value for Return Loss.
These wire pairs must be identified for the tests performed
from each end. Each reported case shall include the frequency
at which it occurs as well as the test limit value at this
frequency.
9. ACR (Attenuation to crosstalk ratio) [This parameter
is not demanded by the standards but may be required in
order to obtain the premise wiring vendor's warranty] ACR
provides an indication of bandwidth for the two wire-pair
network applications. ACR is a computed parameter that is
analogous to ELFEXT and expresses the signal to noise ratio
for a two wire-pair system. This calculation yields 12 combinations
- six from each end of the link. Minimum test results documentation
(summary results): Identify the wire pair combination that
exhibits the worst case margin and the wire pair combination
that exhibits the worst value for ACR. These wire pair combinations
must be identified for the tests performed from each end.
Each reported case shall include the frequency at which
it occurs as well as the test limit value at this frequency.
10. PSACR [This parameter is not required by the
standards but may be required in order to obtain the premise
wiring vendor's warranty]
The Power Sum version of ACR is based on PSNEXT and takes
into account the combined NEXT2 'Margin' designates the
difference between the measured value and the corresponding
test limit value. For passing links, 'worst case margin'
identifies the smallest margin over the entire frequency
range; the point at which the measured performance is "closest"
to the test limit. disturbance of all adjacent wire pairs
on each individual pair. This calculation yields 8 combinations
- one for each wire pair from both ends of the link.
Minimum test results documentation (summary results): Identify
the wire pair that exhibits the worst case margin and the
wire pair that exhibits the worst value for PSACR. These
wire pairs must be identified for the tests performed from
each end. Each reported case shall include the frequency
at which it occurs as well as the test limit value at this
frequency.
11. Propagation Delay [as defined in TIA/EIA-568-B.1;
Section 11.2.4.10]
Propagation delay is the time required for the signal to
travel from one of the link to the other. This measurement
is to be performed for each of the four wire pairs.
Minimum test results documentation (summary results): Identify
the wire pair with the worst case propagation delay. The
report shall include the propagation delay value measured
as well as the test limit value.
12. Delay Skew [as defined in TIA/EIA-568-B.1; Section
11.2.4.11]
This parameter shows the difference in propagation delay
between the four wire pairs. The pair with the shortest
propagation delay is the reference pair with a delay skew
value of zero.
Minimum test results documentation (summary results): Identify
the wire pair with the worst case propagation delay (the
longest propagation delay). The report shall include the
delay skew value measured as well as the test limit value.
C. Test Result Documentation
1. The test results information for each link shall
be recorded in the memory of the field tester upon completion
of the test.
2. The test results records saved by the tester shall
be transferred into a Windows?-based database utility that
allows for the maintenance, inspection and archiving of
these test records. A guarantee must be made that the measurement
results are transferred to the PC unaltered, i.e., "as
saved in the tester" at the end of each test and that
these results cannot be modified at a later time. Superior
protection in this regard is offered by testers that transfer
the numeric measurement data from the tester to the PC in
a non-printable format.
3. The database for the completed job shall be stored
and delivered on CD-ROM including the software tools required
to view, inspect, and print any selection of test reports.
4. A paper copy of the test results shall be provided
that lists all the links that have been tested with the
following summary information
a) The identification
of the link in accordance with the naming
convention
defined in the overall system documentation
b) The overall Pass/Fail
evaluation of the link-under-test including
the NEXT Headroom (overall worst case) number
c) The date and time
the test results were saved in the memory of
the tester
5. General Information to be provided in the electronic
data base with the test results information for each link:
a) The identification
of the customer site as specified by the end-
user
b) The identification
of the link in accordance with the naming
convention defined in the overall
system
documentation
c) The overall Pass/Fail
evaluation of the link-under-test
d) The name of the standard
selected to execute the stored test
results
e) The cable type and
the value of NVP used for length
calculations
f) The date and time
the test results were saved in the memory of
the tester
g) The brand name, model
and serial number of the tester
h) The identification
of the tester interface
i) The revision of the
tester software and the revision of the test
standards database in the tester
j) The test results
information must contain information on each of
the required test parameters that are listed in Section
I.B and
as further detailed below under paragraph I.C.6.
6. The detailed test results data to be provided
in the electronic database for each tested link must contain
the following information (only one of these two formats
must be specified):
a) The results obtained
for each parameter in accordance with the
description
in Section I-B of this document. For each of the
frequency-dependent
test parameters, the value measured at
every
frequency during the test is stored. In this case,
the PC-
resident
database program must be able toprocess the stored
results
to display and print a color graph of the measured
parameters.
The PC-resident software must also provide and
print
the summary numeric information for each test
parameter
as defined and prescribed by the TIA/EIA-568-B.2
standard
document (See Section I-B of this document). A
description
of the summary numeric test report is repeated
under
option b) below.
b) For each of the frequency-dependent
test parameters, the
minimum
test results documentation shall be stored for each
wire-pair
or wire-pair combination as observed from eachend of
the
link. The minimum test results documentation for each test
parameter
shall be in compliance with the information in
Section
I.B.
Length: Identify the wire-pair with the shortest electrical
length, the value of the length rounded to the nearest 0.5
m [optional: foot] and the test limit value
Propagation delay: Identify the pair with the shortest
propagation delay, the value measured in nanoseconds (ns)
and the test limit value
Delay Skew : Identify the pair with the largest value
for delay skew, the value calculated in nanoseconds (ns) and
the test limit value
Insertion Loss (Attenuation): Minimum test results
documentation as explained in Section I.B for the wire pair
with the worst insertion loss
Return Loss: Minimum test results documentation as
explained in Section I.B. Identify as detected from each end
of the link, the wire pair that exhibits the worst case margin
and the wire pair with the worst RL. Each reported case shall
include the frequency at which it occurs as well as the test
limit value at this frequency.
NEXT, ELFEXT, ACR: Minimum test results documentation
as explained in Section I.B. Identify as measured from each
end of the link, the wire pair combination that exhibits the
worst case margin and the wire pair combination that delivers
the worst case value. Each reported case shall include the
frequency at which it occurs as well as the test limit value
at this frequency.
PSNEXT, PSELFEXT, and PSACR: Minimum test results documentation
as explained in Section I.B. Identify as detected from each
end of the link, the wire pair that exhibits the worst case
margin and the wire pair with the worst value. Each reported
case shall include the frequency at which it occurs as well
as the test limit value at this frequency. Link length, propagation
d elay, and delay skew shall be reported for each wire pair
as well as the test limit for each of these parameters.
|