ANSI/TIA/EIA

 

The Specification of Field Test Requirements for Fiber Optic Cabling System

A. General Requirements

1. Every fiber optic cabling link in the installation shall be tested in accordance with the field test specifications defined by the Telecommunications Industry Association (TIA) standard ANSI/TIA/EIA-568-B (or by the appropriate network application standard(s) whichever is more demanding. See Section B.

2. ANSI/TIA/EIA-568-B, defines the passive cabling network, to include cable, connectors, and splices (if present), between two optical fiber patch panels (connecting hardware). A typical horizontal link segment is from the telecommunications outlet/connector to the horizontal crossconnect. This TIA document describes three typical backbone link segments:
    (1) main crossconnect to intermediate cross-connect,
    (2) main cross-connect to horizontal cross-connect,
    (3) intermediate cross-connect to horizontal cross-connect. The            test shall include the representative connector performance at            the connecting hardware associated with the mating of patch            cords. The test does not, however, include the performance of            the connector at the interface with the test equipment.

3. 100% of the installed cabling links must be tested and must pass the requirements of the standards mentioned in A.1 above and as further detailed in Section B. Any failing link must be diagnosed and corrected. The corrective action shall be followed with a new test to prove that the corrected link meets the performance requirements. The final and passing result of the tests for all links shall be provided in the test results documentation in accordance with Section 0 below
.
4. Trained technicians who have successfully attended an appropriate training program and have obtained a certificate as proof thereof shall execute the tests. These certificates may have been issued by any of the following organizations or an equivalent organization:

  • the manufacturer of the fiber optic cable and/or the fiber optic connectors
  • the manufacturer of the test equipment used for the field certification
  •    training organizations authorized by BiCSi (Building Industry Consulting Services
    International with headquarters in Tampa, Florida) or by the ACP (Association of Cabling Professionals Cabling Business Institute located in Dallas, Texas.

    5. Field test instruments for multimode fiber cabling shall meet the requirements of ANSI/TIA/EIA- 526-14A. The light source shall meet the launch requirements of ANSI/EIA/TIA-455-50B, Method A. This launch condition can be achieved either within the field test equipment or by use of an external mandrel wrap (as described in clause 11 of ANSI/TIA/EIA-568-B.1) with a Category 1 light source.
    Field test instruments for singlemode fiber cabling shall meet the requirements of ANSI/EIA/TIA-526-7.

    6. The tester shall be within the calibration period recommended by the vendor in order to achieve the vendor-specified measurement accuracy.

    7. The fiber optic launch cables and adapters must be of high quality and the cables shall not show excessive wear resulting from repetitive coiling and storing of the tester interface adapters.

    8. The Pass or Fail condition for the link-under-test is determined by the results of the required individual tests (detailed in Section I.B).Field Test Specifications for Fiber Optic Installations Page 2 of 4

    9. A Pass or Fail result for each parameter is determined by comparing the measured values with the specified test limits for that parameter.

    10. Optional Requirements:

    11. A representative of the end-user shall be invited to witness field testing. The representative shall be notified of the start date of the testing phase 5 business days before testing commences.

    12. A representative of the end-user will select a random sample of 5% of the installed links. The representative (or his authorized delegate) shall test these randomly selected links and the results are to be stored in accordance with the prescriptions in Section 0. The results obtained shall be compared to the data provided by the installation contractor. If more than 2% of the sample results differ in terms of the pass/fail determination, the installation contractor under supervision of the end-user representative shall repeat 100% testing and the cost shall be borne by the installation contractor.

    B. Performance Test Parameters


    1.
    ANSI/TIA/EIA standard 568-B prescribes that the single performance parameter for field testing of fiber optic links is link attenuation (alternative and equivalent term: insertion loss), when installing components compliant with this standard.

    2.The link attenuation shall be calculated by the following formulas specified in ANSI/TIA/EIAstandard 568-B

    Link Attenuation = Cable_Attn + Connector_Attn + Splice_Attn
    Cable_Attn (dB) = Attenuation_Coefficient (dB/km) * Length (Km)

    The values for the Attenuation_Coefficient are listed in the table below:
    Type of Optical Fiber(dB/km) Wavelength (nm) Attenuation_Coefficient(dB/km)
    Multimode 62.5/125 ��m 850 3.5
      1300 1.5
    Multimode 50/125 ��m 850 3.5
      1300 1.5
    Single-mode(Inside plant) 1310 1.0
      1550 1.0
    Single-mode (Outside plant) 1310 0.5
      1550 0.5

    Connector_Attn (dB) = number_of_connector_pairs * connector_loss (dB)
    Maximum allowable connector_loss = 0.75 dB
    Splice_Attn (dB) = number of splices (S) * splice_loss (dB)
    Maximum allowable splice_loss = 0.3 dB
    Link attenuation does not include any active devices or passive devices other than cable, connectors, and splices, i.e. link attenuation does not include such devices as optical bypass switches, couplers, repeaters, or optical amplifiers.Test equipment that measures the link length and automatically calculates the link loss based on the above formulas is preferred. Field Test Specifications for Fiber Optic Installations Page 3 of 4

    3. The above link test limits attenuation are based on the use of the One Reference Jumper Method specified by ANSI/TIA/EIA-526-14A, Method B and ANSI/TIA/EIA-526-7, Method A.1; or the equivalent method. The user shall follow the procedures established by these standards or application notes to accurately conduct performance testing.

    4. The horizontal link (multimode): acceptable link attenuation for a multimode horizontal optical fiber cabling system is based on the maximum 90 m (295 ft) distance. The horizontal optical fiber cabling link segments need to be tested at only one (1) wavelength. Because of the short length of cabling [90 m (295 ft) or less], attenuation deltas due to wavelength are insignificant. The horizontal link should be tested at 850 nm or 1300 nm in one direction in accordance with ANSI/EIA/TIA-526-14A, Method B, One Reference Jumper method. The horizontal link may be tested using a fixed upper limit for attenuation of 2.0 dB. This value is based on the loss of two (2) connector pairs, one (1) pair at the telecommunications outlet/connector and one (1) pair at the horizontal cross-connect, plus 90 m (295 ft) of optical fiber cable.

    5. The backbone link (multimode) shall be tested in one direction at both operating wavelengths to account for attenuation deltas associated with wavelength.

    6. Multimode backbone links shall be tested at 850 nm and 1300 nm in accordance with ANSI/EIA/TIA-526-14A.
    Because backbone length and the potential number of splices vary depending upon site conditions, the link attenuation equation (Section B.2) shall be used to determine limit (acceptance) values.

    7. Singlemode backbone links shall be tested at 1310 nm and 1550 nm in accordance with ANSI/TIA/EIA-526-7, Method A.1, One Reference Jumper or the equivalent method. All singlemode links shall be certified with test tools using laser light sources at 1310 nm and 1550 nm (See Note below).
    NOTE:a) Link attenuation has been based upon the use of a light source categorized by a Coupled Power Ratio (CPR) of Category 2, Underfilled, per Annex B of ANSI/EIA/TIA-526-14A. The use of a light source categorized as Category 1, Overfilled, may provide results higher than the 2.0 dB limit. A field test tool based on LED (light emitting diode) light sources is a Category 1 device and typically yields high attenuation results.b) Links destined to be used with network applications that use laser light sources (underfilled launch conditions) shall be tested with test equipment based on laser light sources. This rule should be followed for cabling systems to support Gigabit Ethernet. Gigabit Ethernet only specifies laser light sources.
    For Gigabit Ethernet compliant certification (IEEE std 802.3z application), use test equipment which uses a VCSEL (Vertical cavity surface emitting laser) at 850 nm (compliant with 1000BASE-SX) and an FP laser at 1310 nm (compliant with 1000BASELX).

    8. Optional requirement:
    Each fiber optical link terminated with an optical adapter system which does not impose a transmission direction because the adapters are not or cannot be ganged should be tested and documented in both direction since the direction of the signal transmission cannot be predicted at the time of installation.


    C. Test Result Documentation

    1. The test result information for each link shall be recorded in the memory of the field tester upon completion of the test.

    2. The test result records saved by the tester shall be transferred into a Windows?-based database utility that allows for the maintenance, inspection and archiving of these test records.
    A guarantee must be made that these results are transferred to the PC unaltered, i.e., "as saved in the tester" at the end of each test. The popular 'csv' format (comma separated value format) does not provide adequate protection and shall not be acceptable.

    3. The database for the completed job - including twisted-pair copper cabling links if applicable - shall be stored and delivered on CD-ROM; this CD-ROM shall include the software tools required to view, inspect, and print any selection of test reports.

    4. A paper copy of the test results shall be provided that lists all the links that have been tested with the following summary information
          a) The identification of the link in accordance with the naming
               convention defined in the overall system documentation
          b) The overall Pass/Fail evaluation of the link-under-test including
               the Attenuation worst case margin (margin is defined as the
               difference between the measured value and the test limit
               value).
          c) The date and time the test results were saved in the memory of
               the tester

    5. General Information to be provided in the electronic data base containing the test result information for each link:
          a) The identification of the customer site as specified by the end-
               user
          b) The overall Pass/Fail evaluation of the link-under-test
          c) The name of the standard selected to execute the stored test
               results
          d) The cable type and the value of the 'index of refraction' used for
               length calculations
          e) The date and time the test results were saved in the memory of
               the tester
          f) The brand name, model and serial number of the tester
          g) The revision of the tester software and the revision of the test
               standards database in the tester.

    6. The detailed test results data to be provided in the electronic database for each tested optical fiber must contain the following information
          a) The identification of the link/fiber in accordance with the naming
               convention defined in the overall system documentation
          b) The insertion loss (attenuation) measured at each wavelength,
               the test limit calculated for the corresponding wavelength and
               the margin (difference between the measured attenuation and
               the test limit value).
          c) The link length shall be reported for each optical fiber for which
               the test limit was calculated based on the formulas in section
               B.2.

  •   Standard Organization
    Testing Requirement
     
      Twisted Pair
    Optic Fiber
      Testing Standard
      Testing Parameter
      Link/Channel
      Label & File
      Glossary
      FAQ
     
    Girard Electronics Limited
    www.igirard.com | postmaster@igirard.com