Attenuation
Recent changes in the standards now use the term
"insertion loss" and not attenuation. Given that
test equipment manufacturers have used the term attenuation
since 1993, attenuation will continue to be seen on test reports.
Electrical signals transmitted by a link lose some of their
energy as they travel along the link. Insertion loss measures
the amount of energy that is lost as the signal arrives at
the receiving end of the cabling link. The insertion loss
measurement quantifies the effect of the resistance the cabling
link offers to the transmission of the electrical signals.
 |
Insertion loss characteristics of a link change with the
frequency of the signal to be transmitted; e.g. higher frequency
signals experience much more resistance. Stated a different
way, the links show more insertion loss for higher frequency
signals. Insertion loss is therefore to be measured over the
applicable frequency range. If you test the insertion loss
of a Category 5e channel, for instance, the insertion loss
needs to be verified for signals ranging from 1 MHz to 100
MHz. For Cat 3 links the frequency range is 1 through 16 MHz.
Insertion loss also increases fairly linearly with the length
of the link. In other words, if link "A" is twice
as long as link "B", and all other characteristics
are the same, the insertion loss of link "A" will
turn out twice as high as the insertion loss of link "B."
Insertion loss is expressed in decibels or dB. The decibel
is a logarithmic expression of the ratio of output power (power
of the signal received at the end of the link) divided by
input power (the power launched into the cable by the transmitter).
The table below demonstrates that the decibel scale is not
a linear scale.
Results Interpretation
The attenuation in a cable is largely dependent
upon the gauge of wire used in constructing the pairs. 24
gauge wires will have less attenuation than the same length
26 gauge (thinner) wires. Also, stranded cabling will have
20-50% more attenuation than solid copper conductors. Field
test equipment will report the worst value of attenuation
and margin, where the margin is the difference between the
measured attenuation and the maximum attenuation permitted
by the standard selected. Hence a margin of 4 dB is better
than 1 dB.
Troubleshooting Recommendations
Excessive length is the most common reason for
failing attenuation. Fixing links that have failed attenuation
normally involves reducing the length of the cabling by removing
any slack in the cable run.
Excessive attenuation can also be caused by poorly terminated
connectors / plugs. A poor connection can add significant
attenuation. Your clue to this cause is to compare the attenuation
on the four pairs. If only one or two pairs have high attenuation,
this suggests an installation issue. If all pairs have too
much attenuation, check for excess length. However, impurities
in the copper cable can also cause attenuation failures; again
this typically happens on one pair only.
Temperature also affects attenuation in some cables. The
dielectric materials, which form the conductor insulation
and cable jacket, absorb some of the transmitted signal as
it propagates along the wire. This is especially true of cables
containing PVC. PVC material contains a chlorine atom which
is electrically active and forms dipoles in the insulating
materials. These dipoles oscillate in response to the electromagnetic
fields surrounding the wires, and the more they vibrate, the
more energy is lost from the signal. Temperature increases
exacerbate the problem, making it easier for the dipoles to
vibrate within the insulation. This results in increasing
loss with temperature.
For this reason, standards bodies tend to specify attenuation
requirements adjusted for 20 �C. Cables operating in temperature
extremes can be subject to additional attenuation and where
this is likely, the design of the cabling system should take
this into consideration. You may not be able to run the maximum
90 meters (295 ft) defined in the standards. Many consultants
try and keep runs below 80 meters (262 ft) to provide a safety
margin. This of course is not always possible when space is
a premium and the number of telecommunications rooms has to
be kept to a minimum.
|